Description
𝐌𝐨𝐝𝐞𝐥 – XRT10K-U/RM
𝐂𝐚𝐩𝐚𝐜𝐢𝐭𝐲 (𝐕𝐀/𝐖𝐚𝐭𝐭𝐬) – 10000VA/10000W
𝐈𝐍𝐏𝐔𝐓
𝐍𝐨𝐫𝐦𝐢𝐧𝐚𝐥 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 – 220/230/240/Vac
𝐎𝐩𝐞𝐫𝐚𝐭𝐢𝐧𝐠 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐫𝐚𝐧𝐠𝐞 – 120~276Vac
𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲 𝐑𝐚𝐧𝐠𝐞 – 50Hz:45~55Hz ; 60Hz: 54~66Hz (Auto Sensing)
𝐏𝐨𝐰𝐞𝐫 𝐅𝐚𝐜𝐭𝐨𝐫 >= 0.99
𝐁𝐲𝐩𝐚𝐬𝐬 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 𝐑𝐚𝐧𝐠𝐞 –
Max. voltage:
220V: +25% (optional +10%, +15%, +20%)
230V: +20% (optional +10%, +15%)
240V: +15% (optional +10%)
Min. voltage:
-45% (optional -20%, -30%)
𝐁𝐲𝐩𝐚𝐬𝐬 𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲 𝐑𝐚𝐧𝐠𝐞 – Frequency protection range: ±10%
𝐄𝐂𝐎 𝐑𝐚𝐧𝐠𝐞 – Same as the bypass
𝐇𝐚𝐫𝐦𝐨𝐧𝐢𝐜 𝐃𝐢𝐬𝐭𝐨𝐫𝐭𝐢𝐨𝐧 (𝐓𝐇𝐃𝐢) – <3% (100% linear load)
𝐆𝐞𝐧𝐞𝐫𝐚𝐥 𝐈𝐧𝐩𝐮𝐭 – Support
𝐎𝐔𝐓𝐏𝐔𝐓
𝐎𝐮𝐭𝐩𝐮𝐭 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 – 220/230/240/Vac
𝐏𝐨𝐰𝐞𝐫 𝐅𝐚𝐜𝐭𝐨𝐫 – 1.0
𝐕𝐨𝐥𝐭𝐚𝐠𝐞 𝐑𝐞𝐠𝐮𝐥𝐚𝐭𝐢𝐨𝐧 – ±1%
𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲
𝐋𝐢𝐧𝐞 𝐦𝐨𝐝𝐞 (𝐒𝐲𝐧𝐜𝐡𝐫𝐨𝐧𝐢𝐳𝐞𝐝 𝐫𝐚𝐧𝐠𝐞) – ±1%/±2%/±4%/±5%/±10% of the rated frequency (optional)
𝐁𝐚𝐭. 𝐦𝐨𝐝𝐞 – 50/60 (±0.1) Hz
𝐂𝐫𝐞𝐬𝐭 – 3:1
𝐇𝐚𝐫𝐦𝐨𝐧𝐢𝐜 𝐃𝐢𝐬𝐭𝐨𝐫𝐭𝐢𝐨𝐧 (𝐓𝐇𝐃𝐯) – <2% THD (Linear load) / <5% THD (Non-Linear load)
𝐄𝐟𝐟𝐢𝐜𝐢𝐞𝐧𝐜𝐲 – <92% / <93%
𝐁𝐀𝐓𝐓𝐄𝐑𝐘
𝐁𝐚𝐭𝐭𝐞𝐫 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 – ±96/108/120Vdc (optional)
𝐂𝐚𝐩𝐚𝐜𝐢𝐭𝐲 (𝐒𝐭𝐚𝐧𝐝𝐚𝐫𝐝 𝐔𝐧𝐢𝐭) – 12V~7Ah/9Ah
𝐓𝐲𝐩𝐢𝐜𝐚𝐥 𝐑𝐞𝐜𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐓𝐢𝐦𝐞 – 6~8 hours (to 90% of full capacity)
𝐂𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐂𝐮𝐫𝐫𝐞𝐧𝐭 – 1A (Standard unit); Long run unit Max. current 10A (charging current can be set according to battery capacity installed)
𝐒𝐘𝐒𝐓𝐄𝐌 𝐅𝐄𝐀𝐓𝐔𝐑𝐄𝐒
𝐓𝐫𝐚𝐧𝐬𝐟𝐞𝐫 𝐓𝐢𝐦𝐞 – Mains to battery: 0ms , Mains to bypass: 0ms
𝐎𝐯𝐞𝐫𝐥𝐨𝐚𝐝
𝐋𝐢𝐧𝐞 𝐌𝐨𝐝𝐞 – Load<110%: last 10min, <130%: last 1min, >130% turn to bypass made immediately
𝐁𝐲𝐩𝐚𝐬𝐬 𝐌𝐨𝐝𝐞 – 40A(Breaker) / 63A(Breaker) / 80A(Breaker)
𝐒𝐡𝐨𝐫𝐭 𝐂𝐢𝐫𝐜𝐮𝐢𝐭 – Hold whole system
𝐎𝐯𝐞𝐫𝐡𝐞𝐚𝐭 𝐋𝐢𝐧𝐞 𝐦𝐨𝐝𝐞: – Switch to bypass // Back up mode: Shut down UPS immediately
𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐋𝐨𝐰 – Alarm and switch off
𝐁𝐚𝐭𝐭𝐞𝐫𝐲 – Advanced battery management
𝐖𝐚𝐫𝐫𝐚𝐧𝐭𝐲 – 1 Years manufactory warranty.