Description
𝐂𝐚𝐩𝐚𝐜𝐢𝐭𝐲 (𝐕𝐀/𝐖𝐚𝐭𝐭𝐬) 1000VA/1000W
𝐏𝐡𝐚𝐬𝐞 𝐒𝐢𝐧𝐠𝐥𝐞 phase with grounde with
𝐈𝐍𝐏𝐔𝐓
𝐍𝐨𝐫𝐦𝐢𝐧𝐚𝐥 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 200/208/220/230/240/Vac
𝐎𝐩𝐞𝐫𝐚𝐭𝐢𝐧𝐠 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐫𝐚𝐧𝐠𝐞
Low voltage of transferring to bypass
160Vac±5%@100%~80% load 140Vac±5%@80%~70% load 120Vac±5%@70%~60% load 110Vac±5%@60%~0% load (Ambient Temp. <35C)
Low threshold voltage of recovering from bypass
175Vac±5%@100%~80% load 155Vac±5%@80%~70% load 135Vac±5%@70%~60% load 125Vac±5%@60%~0% load (Ambient Temp. <35C)
𝐇𝐢𝐠𝐡 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐨𝐟 𝐭𝐫𝐚𝐧𝐬𝐟𝐞𝐫𝐫𝐢𝐧𝐠 𝐭𝐨 𝐛𝐲𝐩𝐚𝐬𝐬 300Vac±5%
𝐇𝐢𝐠𝐡 𝐭𝐡𝐫𝐞𝐬𝐡𝐨𝐥𝐝 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 𝐨𝐟 𝐫𝐞𝐜𝐨𝐯𝐞𝐫𝐢𝐧𝐠 𝐟𝐫𝐨𝐦 𝐛𝐲𝐩𝐚𝐬𝐬 290Vac±5%
𝐎𝐩𝐞𝐫𝐚𝐭𝐢𝐧𝐠 𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲 𝐑𝐚𝐧𝐠𝐞 40~70Hz
𝐆𝐞𝐧𝐞𝐫𝐚𝐭𝐨𝐫 𝐈𝐧𝐩𝐮𝐭 Support
𝐎𝐔𝐓𝐏𝐔𝐓
𝐎𝐮𝐭𝐩𝐮𝐭 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 200/208/220/230/240/Vac
𝐏𝐨𝐰𝐞𝐫 𝐅𝐚𝐜𝐭𝐨𝐫 1.0
𝐕𝐨𝐥𝐭𝐚𝐠𝐞 𝐑𝐞𝐠𝐮𝐥𝐚𝐭𝐢𝐨𝐧 ±1%
𝐅𝐫𝐞𝐪𝐮𝐞𝐧𝐜𝐲
𝐋𝐢𝐧𝐞 𝐦𝐨𝐝𝐞 (𝐒𝐲𝐧𝐜𝐡𝐫𝐨𝐧𝐢𝐳𝐞𝐝 𝐫𝐚𝐧𝐠𝐞) 47~53Hz or 57~63Hz
𝐁𝐚𝐭. 𝐦𝐨𝐝𝐞 (50/60±0.1)Hz
𝐂𝐫𝐞𝐬𝐭 3:1
𝐇𝐚𝐫𝐦𝐨𝐧𝐢𝐜 𝐃𝐢𝐬𝐭𝐨𝐫𝐭𝐢𝐨𝐧 (𝐓𝐇𝐃𝐯) <2% THD (Linear load) / <4% THD (Non-Linear load)
𝐖𝐚𝐯𝐞𝐟𝐨𝐫𝐦 Pure Sineswave
𝐓𝐫𝐚𝐧𝐬𝐟𝐞𝐫 𝐓𝐢𝐦𝐞
𝐀𝐂 𝐦𝐨𝐝𝐞 <-> 𝐁𝐚𝐭𝐭. 𝐌𝐨𝐝𝐞 Zero
𝐈𝐧𝐯𝐞𝐫𝐭𝐞𝐫 <-> 𝐁𝐲𝐩 4ms (Typical)
𝐁𝐀𝐓𝐓𝐄𝐑𝐘
𝐁𝐚𝐭𝐭𝐞𝐫 12V9AH
𝐍𝐮𝐦𝐛𝐞𝐫𝐬 2
𝐁𝐚𝐜𝐤𝐮𝐩 𝐓𝐢𝐦𝐞
Long run unit depends on the capacity of externel batteries
𝐓𝐲𝐩𝐢𝐜𝐚𝐥 𝐑𝐞𝐜𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐓𝐢𝐦𝐞 (𝐒𝐭𝐚𝐧𝐝𝐚𝐫𝐝 𝐌𝐨𝐝𝐞) 4 hours recover to 90% capacity
𝐂𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐕𝐨𝐥𝐭𝐚𝐠𝐞 27.4VDC±1%
𝐂𝐡𝐚𝐫𝐠𝐢𝐧𝐠 𝐂𝐮𝐫𝐫𝐞𝐧𝐭 (𝐌𝐚𝐱.) 1A or 2A
𝐒𝐘𝐒𝐓𝐄𝐌 𝐅𝐄𝐀𝐓𝐔𝐑𝐄𝐒
𝐋𝐢𝐧𝐞 𝐌𝐨𝐝𝐞 𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐌𝐨𝐝𝐞
𝐀𝐦𝐛𝐢𝐞𝐧𝐭 𝐓𝐞𝐦𝐩. <𝟑𝟓 𝐂
105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal
110%~130%: UPS transfer to bypass after 1 minute when the utility is normal
130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal
>150%: UPS transfer to bypass immediately when the utility is normal
𝟑𝟓 𝐂 <𝐀𝐦𝐛𝐢𝐞𝐧𝐭 𝐓𝐞𝐦𝐩. <𝟒𝟎 𝐂
105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal
110%~130%: UPS transfer to bypass after 1 minute when the utility is normal
>130%: UPS transfer to bypass immediately when the utility is normal
𝐒𝐡𝐨𝐫𝐭 𝐂𝐢𝐫𝐜𝐮𝐢𝐭 Hold whole system
𝐎𝐯𝐞𝐫𝐡𝐞𝐚𝐭 𝐋𝐢𝐧𝐞 𝐦𝐨𝐝𝐞: Switch to bypass; Back up mode: Shut down UPS immediately
𝐁𝐚𝐭𝐭𝐞𝐫𝐲 𝐋𝐨𝐰 Alarm and switch off
𝐄𝐏𝐎 (𝐎𝐩𝐭𝐢𝐨𝐧𝐚𝐥) Shut down UPS immediately
𝐀𝐮𝐝𝐢𝐛𝐥𝐞 & 𝐕𝐢𝐬𝐮𝐚𝐥 𝐀𝐥𝐚𝐫𝐦𝐬 Line failure, Battery low, Overload, System fault
𝐂𝐨𝐦𝐦𝐮𝐧𝐢𝐜𝐚𝐭𝐢𝐨𝐧 𝐈𝐧𝐭𝐞𝐫𝐟𝐚𝐜𝐞 USB, RS232, SNMP card (optional), Relay card (optional)
𝐖𝐚𝐫𝐫𝐚𝐧𝐭𝐲 1 Years manufactory warranty.